FST-DC900V-930KW-R DC LOAD BANK

Categories:

FST-DC900V-930KW-R DC LOAD BANK

Additional information

Load Element

Stainless steel resistors

Load Voltage

DC900V

Load Power

Total: 930KW

(Channel 1:465KW, Channel 2: 465KW)

Load Channel

2 independent load channel, each channel 900V 465KW

Load Steps @DC900V

Channel 1: 60kW*7 resistors (12.8 Ohm), 15kW*3 resistors (51 Ohm) (Load step ON/OFF by client’s IGBT)

Channel 2: 60kW*7 resistors (12.8 Ohm), 15kW*3 resistors (51 Ohm) Load step ON/OFF by client’s IGBT)

Load Accuracy

±5%

Work Mode

Continuous

Digital Meter

Voltage, current, power for each load channel

Fan meter to detect fan working condition

Power Supply

AC380V 3phase 4wire, 60Hz (ON/OFF by 220V contactor coil)

Control Mode

By client’s control bench

Wire Connections

Copper bus bar for wire connections for the 2 load channel

Insulation Class

F

Protection Level

IP20(indoor use)

Fan Noise

75dB

Cooling Mode

Force-air vertical cooling

Protections

Over voltage/current/heat alarm for each load channel.

Fan over voltage & low current alarm.

Ambient Temperature

-10℃~+50℃

Dimension

1600*1850*1800mm(W*D*H)(final dimension to be designed)

Weight

Around 1.2T

Mobility

Stationary with forklift pocket

Humidity

≤95%

Altitude

≤2500 meters