Additional information
| Load Element | Stainless steel resistors |
|---|---|
| Load Voltage | DC900V |
| Load Power | Total: 930KW (Channel 1:465KW, Channel 2: 465KW) |
| Load Channel | 2 independent load channel, each channel 900V 465KW |
| Load Steps @DC900V | Channel 1: 60kW*7 resistors (12.8 Ohm), 15kW*3 resistors (51 Ohm) (Load step ON/OFF by client’s IGBT) Channel 2: 60kW*7 resistors (12.8 Ohm), 15kW*3 resistors (51 Ohm) Load step ON/OFF by client’s IGBT) |
| Load Accuracy | ±5% |
| Work Mode | Continuous |
| Digital Meter | Voltage, current, power for each load channel Fan meter to detect fan working condition |
| Power Supply | AC380V 3phase 4wire, 60Hz (ON/OFF by 220V contactor coil) |
| Control Mode | By client’s control bench |
| Wire Connections | Copper bus bar for wire connections for the 2 load channel |
| Insulation Class | F |
| Protection Level | IP20(indoor use) |
| Fan Noise | 75dB |
| Cooling Mode | Force-air vertical cooling |
| Protections | Over voltage/current/heat alarm for each load channel. Fan over voltage & low current alarm. |
| Ambient Temperature | -10℃~+50℃ |
| Dimension | 1600*1850*1800mm(W*D*H)(final dimension to be designed) |
| Weight | Around 1.2T |
| Mobility | Stationary with forklift pocket |
| Humidity | ≤95% |
| Altitude | ≤2500 meters |