Published On: 03/20/2025Categories: 未分类

Liquid AC load bank

Table Of Content

Technical parameter
1. The rated power of a single cabinet is 36kW (the power can be adjusted according to demand).
2, power error rate under rated working conditions (voltage 225V, water temperature 35℃-45℃) ≤5%
3, power regulation “1 group, phase A 1kW+2kW+3kW, phase B 1kW+2kW+3kW, phase C 1kW+2kW+3kW
2 groups, phase A 3kW+3kW, phase B 3kW+3kW, phase C 3kW+3kW A total of 6 groups of switches, 6 groups of switches between independent power supply”
4, control mode 15 2P AC DC universal switch control, 1kW power switch is not less than 10A, 2kW, 3kW power switch is not less than 20A, divided into 2 groups, corresponding to the above power segment in turn
5, allow the working environment temperature -10℃~+70℃
6, alarm form sound and light alarm
7, the power supply interface by 6 single-phase 32A 3-hole industrial connectors access to 6 groups of power supply work, respectively, 1 group A, 1 group B, 1 group C, 2 groups A, 2 groups B, 2 groups C. Each industrial connector extends three C14 power cables with a length of 2m.
(Two 3-phase 5-wire PDUs are provided for the owner under the field use condition, which are powered by different power sources, and the 6 industrial connectors with fake loads need to be independent respectively.) “

Share with your friend

About the Author: Foresight

Foresight
Foresight Electronics Co, Ltd. is engaged in the high-tech enterprise specially engaged in R&D and production and marketing of all kinds of products involved in high quality contact less laser distance measurement.

Leave A Comment