Description
| System Parameters | |
| Rating Voltage/Frequency | (A/B/C/N),AC400V/50Hz。
AC400VAC,3 phase 4wire,50Hz,。
|
| Rated Load Power | Resistive load: 200kW。 |
| Load Step
(AC400V/50Hz)
|
Resistive load:9 step,
1、2、2、5、10、20、40、40、80kW。 |
| PF (Power Factor) | 1 |
| Load Tolerance
(each step) |
±5% |
| Load Tolerance(overall) | ±3% |
| Display Precision | 0.5 class |
| Control Power | 240VAC/50Hz,1phase 2 wire,AC110~240V 1-Phase |
| Wire Connection | Load power supply input——Copper bar (star coupling),
Control power supply input——Three-core power supply; |
| Communication Interface | RS485; |
| Insulation | F |
| Duty Cycle | Continuous; |
| Cooling Type | Force air cooling, Crosswind and Crosswind。 |
| Transportation | Hoisting, there are lifting lug on top and castors at the bottom of casing |
| Color | Oxidized white; |
| Dimension | About 748mm×509mm×660.5mm(L×W×H)。 |
| Weight | About75kgs。 |
| Operating Environment Parameter | |
| Ambient Temperature | -20℃~+50℃; |
| Relative Humidity | ≤95%; |
| Altitude | ≤2500m
meter; |
| Atmospheric Pressure | 86~106kPa; |
| Brands of Main Components | |
| Contactor | Schneider |
| Alloy Resistance | FORESIGHT(self-developed) |
| Data Processing Software | FORESIGHT |








Reviews
There are no reviews yet.