400V/500V 400A HV-EV Battery Load Bank

Categories:

Applications

  • Discharge Testing
  • Battery Capacity Testing
  • Acceptance Testing
  • Battery Maintenance
  • Engineer Testing

Description

These smart DC load banks are designed for battery capacity testing, discharge testing, battery maintenance and other testing with DC power with a load. These series are easy-to-use, portable and economic. Foresight Electronic load banks are designed specifically to make discharge testing easy for any application.

 

 

 

 

 

 

 

Features

  • SMART Constant Current DC Load Banks with system and cell voltage monitoring
  • Data management software included for data analyzing and reporting
  • Rugged, compact and portable units
  • Alloy and PTC resistors for safe discharging
  • Four settings for auto shut-down of discharge: discharge time, total string end voltage, cell end voltage, discharged capacity
  • Parallel connection of two units for mass discharge testing
  • Thermal cut-off and automatic overload protection
  • Safe circuits avoid damage to battery when testing
  • Optional: Real-time display of voltage for each cell with DAC package for 1.2V, 2V, 4V,6V, 12V cells
  • Optional: Custom DAC packages available for monitoring of uncommon cell voltages and configurations

 

Features Specifications
Model  FST-DC400V-400A
DC Voltage measurement
DC Voltage Range 400V
Accuracy & resolution ≤±0.5%, 0.01V
DC Voltage measurement
Internal current range 2-400A
Accuracy & resolution ≤ ± 1% , 0.1A
Cell voltage Range 0-15V
Accuracy & resolution ≤ ± 0.5%, 0.01 V
AC POWER SUPPLY
Power Supply 220VAC 50Hz
Cooling mode Air Cooling
Communication & Storage
Storage mode SD Card and Internal storage
Internal memory 16Mbit Flash or Optional
Display 7inch Touch screen
High-Voltage insulation test Input-The enclosure:2200Vdc 1min

Input-Output:2200Vdc 1min

Output- The enclosure:700Vdc 1min

Safety standard EN610950
CE Certificate LVD: EN61010-12010; EMC:EN61326-1:2013
Environment
Work Temperature -5~50℃
Storage Temperature -40~70℃
Humidity Relative humidity 5%~95%
Altitude below 4000 m
Working Noise <60dB
Net Weight(KG) About 120

 

 

 

Reviews

There are no reviews yet.

Be the first to review “400V/500V 400A HV-EV Battery Load Bank”

Your email address will not be published. Required fields are marked *

Related Product

Title

Go to Top