FST-CT/PT Variable frequency intelligent transformer tester

Main Function Features

Comprehensive functions, meeting the testing
requirements for various types of CTs (such as
protection, metering, and TP types) including excitation
characteristics (i.e., volt-ampere characteristics),
transformation ratio, polarity, secondary winding
resistance, secondary load, ratio error, and phase angle
error, as well as for various PT electromagnetic units
including excitation characteristics, transformation
ratio, polarity, secondary winding resistance, ratio
error, and phase angle error.

Description

Automatically provides knee-point voltage/current, 10% (5%)
error curve, accurate limit factor (ALF), instrument security factor
(FS), secondary time constant (Ts), residual magnetism coefficient
(Kr), saturated and unsaturated inductance, and other CT and PT
parameters.

Tests comply with standards such as GB20840.1 (IEC60044-1), GB20840.2 (IEC60044-6),
and GB20840.3 for various types of transformers, and automatically selects the appropriate standard
for testing based on the type and level of the transformer.

Based on advanced low-frequency testing principles, it can handle CT tests with knee points up to
45kV.
.The device can store 2000 sets of test data without loss upon power failure. After the test is
XIAN FORESIGHT ELECTRONIC TECHNOLOGY CO., LTD.
completed, the data can be saved to a PC via a USB drive, and analyzed using software to generate
a WORD report.

Testing is simple and convenient, with one button to complete CT direct resistance, excitation,
transformation ratio, and polarity tests. Except for load tests, all other CT tests use the same wiring
method.。

DC resistance, excitation ratio experiment connection

Secondary load experiment connection

Technical Parameter
The Model
FST-CT/PT Variable frequency intelligent transformer tester

XIAN FORESIGHT ELECTRONIC TECHNOLOGY CO., LTD.
Usage Class P/TP CT & VT
Output 0~180Vrms,12Arms,36A(peak value)
Voltage measurement accuracy ±0.2%
CT Ratio
Range 1~40000
accuracy ±0.2%
PT Ratio
Range 1~40000
accuracy ±0.2%
Phase
Range ±5min
accuracy 0.5min
DC resistance
Range 0~300Ω
accuracy 2%±2mΩ
Burden
Range 0~300VA
accuracy 2%±0.2VA
Power supply AC220V±10%,50Hz
Environmental Conditions Operating temperature :-10οC ~50οC,Humidity :≤90%
Weight and Dimensions Dimensions:340mm x220mmx330mm ,Weight<9kg
Aluminum alloy box dimensions 430mm x270mm x500mm

Reviews

There are no reviews yet.

Be the first to review “FST-CT/PT Variable frequency intelligent transformer tester”