400V 1000KW Resistive AC Load Bank for Genertor loading test indoor use
Table Of Content
| AC400V-1000kW Resistive Load Bank | |
| Rating Voltage/Frequency | 400VAC, 3 phase 4wire 50Hz/60Hz |
| Rated Load Power | 1000kW |
| Load Step | 1kW,2kW,2kW,5kW,10kW,10kW,20kW,50kW,100kW,200kW,200kW,
200kW,200kW, min step load: 1kW Through the combination of these load steps could load 1kW,2kW,3kW,4kW,5kW,6kW,7kW,8kW,9kW,10kW,11kW,12kW, 13kW,14kW,15kW…….till 1000kW, step value 1kW |
| PF(Power Factor) | 1 |
| Load Tolerance (each step) | ±5% |
| Load Tolerance(overall) | ±3% |
| Display Precision | 0.5 class |
| Control Power | External 380VAC, 3 phase 4wire 50Hz |
| Wire Connection | Load power supply input——Copper bar (star coupling)
Control power supply input——Connector-bar |
| Insulation | F |
| Duty Cycle | Continuous |
| Cooling Type | Force air cooling, horizontal air inlet & air outlet, with louvers for protection |
| Ingress Protection | IP54 |
| Enclosure | Weatherproof |
| Transportation | Hoisting, there are lifting lug on top |
| Dimension | About 1800mm*1300mm*1930mm(L×W×H) |
| Weight | About 1300kgs |
| Enclosure Color | As required |
| Operating Environment Parameter | |
| Workplace | Outdoor or indoor |
| Ambient Temperature | -20℃~+50℃ |
| Relative Humidity | ≤95% |
| Altitude | ≤2500 meter |
| Atmospheric Pressure | 86~106kPa |
| Brands of Main Components | |
| Contactor | Schneider |
| Fuse | Miro |
| PLC | Siemens |
| Data processing software | (self-developed) |
| Alloy Resistance | (self-developed) |