FST-CDT48V-300A Battery Charge & Discharge Tester
FST-CDT Intelligent Battery Regenerator
-Charger+ Discharger +Regeneration Function
FST-CDT Battery charge/discharge tester is integrated with constant current discharging, cell voltage collection and intellectualized charging, it provides comprehensive scientific test methods for stationary battery and UPS Power system and is widely applied in the field of Telecommunications, Base station and Utilities etc.
◆Main Features & Function:
Stationary Battery String Charge/Discharge all in-one-machine = Constant Current Discharge + Intelligent Charge + Cell Voltage Collection + Stationary string Regeneration
Description
- Charge-Discharge to battery string removed from the system
- Discharge to Battery string voltage as 48V-60V, Cell voltage as 2V/6V/12V
- 4 adjustable stop points and multiple alarm designs to control the discharge process intelligently
- 7inch LCD touch screen for easy operation and showing various parameters real time
- Support real on line monitoring on the PC or SD Card download data after discharge
- PC software for capacity evaluation and report generation
Constant current discharge, Intelligent charge in three phases and real time collecting cell parameters on line,to setup voltage, current, time and capacity on the LCD,Automatically finishing all the tests under setup. Monitoring, Regeneration, on line or offline monitoring the voltage of battery string and cell voltage.
Discharge under constant current and constant power.
Technical Specifications
Type | FST-CDT48VDC-300A |
Test mode of Charge-Discharge | Battery String removing from the System |
Discharge Current | 1-300A |
Discharge Current Accuracy | Resolution: 0.1A Accuracy: 1A |
Charge Current | 1-300A |
Charge Current Accuracy | Resolution: 0.1A Accuracy: 1A |
Discharge Voltage | 48V |
Discharge Voltage Accuracy | Resolution: 10mV Accuracy: 0.1V |
Charge Voltage | 48V |
Charge Voltage Accuracy | (Resolution: 10mV Accuracy: 0.1V) |
Cell Voltage of Charge-Discharge | 0.500V~16.00V(Resolution :1mV Accuracy 10mV) |
Time of Charge-Discharge | 0~99h59min |
Number of Cell | Set according to the actual situation |
Cooling Mode | Forced air cooling type |
Discharge Load | High performance alloy resistance |
Display | 7” Color Touch Screen |
Power Supply | Three phase AC380V±10% 3 Phase 4 wires |
Alarm and safety measures | Reverse connection protection, over voltage and over current protection;Abnormal temperature, Fan Fault etc。 the tester can alarm and stop the test |
Reviews
There are no reviews yet.