FST-DC110V-300A Battery Load Bank
Battery load bank is a powerful and lightweight solution designed for condition assessment of telecommunication and radio equipment backup supply. This instrument can perform the battery capacity test on battery strings such as Pb, Li-ion, Ni-Cd, and others
Discharge parameters can be monitored in real-time during the capacity test. A 5,7-inch touch screen shows overall battery voltage, discharge current, discharge test time, and capacity during the entire test
Features
- SMART Constant Current DC Load Banks with system and cell voltage monitoring
- Data management software included for data analyzing and reporting
- Rugged, compact and portable units
- Alloy and PTC resistors for safe discharging
- Four settings for auto shut-down of discharge: discharge time, total string end voltage, cell end voltage, discharged capacity
- Parallel connection of two units for mass discharge testing
- Thermal cut-off and automatic overload protection
- Safe circuits avoid damage to battery when testing
- Optional: Real-time display of voltage for each cell with DAC package for 1.2V, 2V, 6V, 12V cells
- Optional: Custom DAC packages available for monitoring of uncommon cell voltages and configurations
Applications
- Discharge Testing
- Battery Capacity Testing
- Acceptance Testing
- Battery Maintenance
- Engineer Testing
Description
Features | Specifications | |
Model | FST-DC100V-300A | |
DC Voltage measurement | ||
Discharge Voltage of Constant current and constant power | 90V~150VDC | |
Discharge power in constant power mode | 80-33000W or higher, Stepless control | |
Accuracy & resolution | ≤±0.5%, 0.01V | |
DC Voltage measurement | ||
Internal current range | 0-300A | |
Accuracy & resolution | ≤ ± 1% , 0.1A | |
Cell voltage Range | 0-15V | |
Accuracy & resolution | ≤ ± 0.5%, 0.01 V | |
AC POWER SUPPLY | ||
AC POWER SUPPLY | 220VAC-15% +25% 50Hz/60Hz | |
Cooling mode | Air Cooling | |
Communication & Storage | ||
Communication Mode | USB Port | |
Internal memory | 16Mbit Flash | |
Display | 7inch Touch screen | |
High-Voltage insulation test | Input-The enclosure:2200Vdc 1min
Input-Output:2200Vdc 1min Output- The enclosure:700Vdc 1min |
|
Safety standard | EN610950 | |
CE Certificate | LVD: EN61010-12010; EMC:EN61326-1:2013 | |
Environment | ||
Work Temperature | -5~50℃ | |
Storage Temperature | -40~70℃ | |
Humidity | Relative humidity 5%~95% | |
Altitude | below 4000 m | |
Working Noise | <60dB | |
Dimensions of Host machine | 600×225×x630 | |
Net Weight | ≤ 75kg |